Broken input selection (bits 6 and 7), Broken input selection (bits 6 and 7) -16 – Rockwell Automation 1746-NR8 SLC 500 RTD/Resistance Input Module User Manual User Manual

Page 64

Advertising
background image

Publication 1746-UM003A-EN-P

4-16 Channel Configuration, Data, and Status

The following two tables show the data resolution provided by the 1746-NR8
for resistance input types using the various data formats.

Table 4.18 Channel Data Word Resolution for 150

Resistance Input

Table 4.19 Channel Data Word Resolution for 500

, 1000

, and 3000

Resistance

Inputs

Broken Input Selection (Bits 6 and 7)

The next table shows the descriptions for bits 6 and 7. The broken input bit
field lets you define the state of the channel data word when an open-circuit or
short-circuit condition is detected for that channel.

An open-circuit condition occurs when the RTD or potentiometer or its
extension wire is physically separated or opened. This can happen if the wire is
cut or disconnected from the terminal block.

The short-circuit condition applies only to RTD input types. This can happen
if the RTD or its signal wires are shorted together for any reason. The
short-circuit condition does not apply to resistance ranges since they start at 0
ohms, which can be a short-circuit condition.

Table 4.20 Bit Descriptions for Broken Input Selection

Resistance
Input Type

Data Format (Bits 4 and 5)
Engineering Units
x 1

Engineering
Units x 10

Scaled-for-PID Proportional

Counts
(Default)

Ohms

Ohms

Ohms

Ohms

150

0.01

/step

0.1

/step

0.0092

/step

0.0023

/step

Resistance
Input Type

Data Format (Bits 4 and 5)
Engineering Units
x 1

Engineering
Units x 10

Scaled-for-PID Proportional

Counts
(Default)

Ohms

Ohms

Ohms

Ohms

500

0.1

/step

1

/step

0.0305

/step

0.0076

/step

1000

0.1

/step

1

/step

0.0610

/step

0.0153

/step

3000

0.1

/step

1

/step

0.1831

/step

0.0458

/step

Binary
Value

Select

Description

00

Zero

Force the channel data word to 0 during an open-circuit condition
or short-circuit condition.

01

Upscale

Force the channel data word value to its full scale value during an
open-circuit or short-circuit condition. The full scale value is
determined by the input type, data format, and scaling selected.

10

Downscale Force the channel data word value to its low scale value during

an open-circuit or short-circuit condition. The low scale value is
determined by the input type, data format, and scaling selected.

Advertising