6-6 Module Diagnostics and Troubleshooting

Figure 6.2 Troubleshooting Flowchart

Check LEDs
on module.

Module Status
LED is off.

Module Status
LED is on.

Channel Status
LED(s) is
flashing.

Channel Status
LED is off.

Channel Status
LED is on.

Module fault
condition

Normal module
operation

Fault

condition

Channel is not

enabled.

Channel is
enabled and
working properly.

Check to see
that module is
seated properly
in chassis.
Cycle power.

Check channel
status word
bits 13 to 15

Enable channel if
desired by setting
channel config.
word (bit 11=1).

Retry.

End

End

End

Configuration error.
Check and correct the
configuration word for
this channel.

Out-of-range error
indicating that either an
over-range or under-range

condition exists. For all
over-range, the input signal
is greater than the high
scale limit for the channel.
For under-range, the input
signal is less than the low

scale limit for the channel.

Bit 15
set (1)

Bit 14
set (1)

Bit 13
set (1)

Yes

No

Yes

No

Contact your
local distributor
or Rockwell
Automation.

Contact your
local distributor
or Rockwell
Automation.

Is problem
corrected?

Is problem
corrected?

A broken input error or
short-circuit (RTD)
condition is present. Check
channel for open or loose
connections (RTD and
potentiometer inputs) and
check channel for
short-circuit condition (RTD
only). Retry.