Scaling examples, Scaled-for-pid to engineering units, Engineering units to scaled-for-pid – Rockwell Automation 1746-NR8 SLC 500 RTD/Resistance Input Module User Manual User Manual

Page 59

Advertising
background image

Publication 1746-UM003A-EN-P

Channel Configuration, Data, and Status 4-11

Scaling Examples

The following examples are using the default scaling ranges:

Scaled-for-PID to Engineering Units

Equation:

Assume that the input type is an RTD, Platinum (200

, a = 0.00385°C,

range = -200°C to +850°C), scaled-for-PID display type. Channel data = 3421.

Want to calculate °C equivalent.

From Channel Data Word Format, S

LOW

= -200°C and S

HIGH

= 850°C.

Solution:

Solution:

Solution:

Solution:

Engineering Units to Scaled-for-PID

Equation:

Assume that the input type is an RTD, Platinum (200

, a = 0.00385°C,

range = -200°C to +850°C), scaled-for-PID display type. Desired channel
temperature = 344°C.

Want to calculate Scaled-for-PID equivalent.

From Channel Data Word Format, S

LOW

= -200°C and SHIGH = 850°C.

Solution:

Engr Units Equivalent

SLOW

SHIGH - SLOW

(

)

Scaled-for-PID value displayed

16383

-------------------------------------------------------------------------------

×

+

=

Engr Units Equivalent

200°C

850°C - (-200°C)

(

)

3421

16383

---------------

×

19.25°C

=

+

=

Scaled-for-PID Equivalent

16383

Engr Units desired - SLOW

(

)

SHIGH - SLOW

(

)

--------------------------------------------------------------------------

×

=

Scaled-for-PID Equivalent

16383

344°C

-200°C

(

)

+

850°C- (-200°C)

-----------------------------------------------

Ч

8488

=

=