4-14 Channel Configuration, Data, and Status

The following tables show the resistance ranges provided by the 1746-NR8.

Table 4.9 Data Format for 150

Resistance Input

Table 4.10 Data Format for 500

and 1000

Resistance Input

Table 4.11 Data Format for 3000

Resistance Input

The following table shows the data resolution provided by the 1746-NR8 for
RTD input types using the various data formats. The table applies to both 0.25
and 1.0 mA excitation currents. The data resolution of the remaining RTDs
vary with excitation current.

Table 4.12 Channel Data Word Resolution for RTDs

Resistance Input Type

Data Format
Engineering Units x 1

Engineering Units x 10

Scaled-for-PID

Proportional Counts
(Default)

0.01

(1)

0.1

(1)

150

0 to 15000

0 to 1500

0 to 16383

-32768 to 32767

(1) When ohms are selected, the temperature-units selection (bit 8) is ignored.

Resistance Input Type

Data Format
Engineering Units x 1

Engineering Units x 10

Scaled-for-PID

Proportional Counts
(Default)

0.1

(1)

1.0

(1)

500

0 to 5000

0 to 500

0 to 16383

-32768 to 32767

1000

0 to 10000

0 to 1000

0 to 16383

-32768 to 32767

(1) When ohms are selected, the temperature-units selection (bit 8) is ignored.

Excitation Current

Data Format
Engineering Units x 1

Engineering Units x 10

Scaled-for-PID

Proportional Counts
(Default)

0.1

(1)

1.0

(1)

0.25 mA

0 to 30000

0 to 3000

0 to 16383

-32768 to 32767

1.0 mA

0 to 12000

0 to 1200

0 to 16383

-32768 to 32767

(1) When ohms are selected, the temperature-units selection (bit 8) is ignored.

RTD Input Type

Data Format (Bits 4 and 5)

(1)

Engineering Units x 1

Engineering Units x
10

Scaled-for-PID

Proportional Counts
(Default)

°C

°F

°C

°F

°C

°F

°C

°F

100

Platinum 385

0.1°C/step 0.1°F/step

1°C/step

1°F/step

0.0641°C/step 0.1154°F/step 0.0160°C/step 0.0288°F/step

200

Platinum 385

0.1°C/step 0.1°F/step

1°C/step

1°F/step

0.0641°C/step 0.1154°F/step 0.0160°C/step 0.0288°F/step

100

Platinum 3916

0.1°C/step 0.1°F/step

1°C/step

1°F/step

0.0507°C/step 0.0912°F/step 0.0127°C/step 0.0228°F/step

200

Platinum 3916

0.1°C/step 0.1°F/step

1°C/step

1°F/step

0.0507°C/step 0.0912°F/step 0.012 °C/step 0.0228°F/step

10

Copper 426

0.1°C/step 0.1°F/step

1°C/step

1°F/step

0.0220°C/step 0.0396°F/step 0.0051°C/step 0.0099°F/step

120

Nickel 618

(2)

0.1°C/step 0.1°F/step

1°C/step

1°F/step

0.0220°C/step 0.0396°F/step 0.0051°C/step 0.0099°F/step

120

Nickel 672

0.1°C/step 0.1°F/step

1°C/step

1°F/step

0.0208°C/step 0.0374°F/step 0.005 °C/step 0.0093°F/step

(1) When ohms are selected, the temperature-units selection (bit 8) is ignored. Analog input data is the same for either °C or °F selection.

(2) Actual value at 0°C is 100

per DIN standard.