Publication 1746-UM003A-EN-P

7-4 Application Examples

Figure 7.3 Device Configuration for Displaying Many RTD Inputs

Channel Configuration

(see completed worksheet on page 7-5)

Configuration setup for ambient RTD:

channels 0 and 4

604

Nickel/Iron (518)

display temperature to tenths of a degree Celsius or Fahrenheit

zero data word in the event of an open- or short-circuit

28 Hz input filter to provide 60 Hz line noise rejection

use 1.0 mA excitation current for RTD

scaling for -20°C to +60°C

Bath

°

C

°

F

.

Chilled H

2

O

Steam

.

.

Ambient

.

.

.

.

SLC 5/04

1746-NR8

1746-IB8

(8) 1746-OB16

Ambient Temperature
604

Nickel/Iron (518)

Chilled H

2

O Pipe In

Chilled H

2

O Pipe Out

200

Platinum RTD (385)

1000

Platinum RTD (385)

Steamed Pipe Out

Steamed Pipe In

Bath

200

Platinum RTD (385)

Display Panel

Selector Switch (I:2/0)

Ambient Temperature
604

Nickel/Iron (518)

Bath

200

Platinum

RTD (385)

Chilled H

2

O Pipe In

Chilled H

2

O Pipe Out

200

Platinum RTD (385)

1000

Platinum RTD (385)

Steamed Pipe Out

Steamed Pipe In