Rockwell Automation 1746-NR8 SLC 500 RTD/Resistance Input Module User Manual User Manual

Page 19

Advertising
background image

Publication 1746-UM003A-EN-P

Overview 1-9

Figure 1.4 LED Indicators

The purpose of the LEDs is as follows:

Channel Status - One LED for each of the 8 input channels indicates if the
channel is enabled, disabled, or is not operating as configured, due to an
error.

Module Status - If OFF or flashing at any time, other than at powerup, this
LED indicates that non-recoverable module errors (for example, diagnostic
or operating errors) have occurred. The LED is ON if there are no module
errors.

The status of each LED, during each of the operational states (for example,
powerup, module operation and error), is depicted in the following table.

LED

Power-up

(1)

(1) Module is disabled during powerup.

Module Operation
(No Error)

(2)

(2) Channel status LED is On if the respective channel is enabled and Off if the channel is disabled.

Module Error

Channel
Error

Ch 0 to 7 Status On

On/Off

Off

(3)

(3) Error if channel is enabled.

Flashes

Mod. Status

Off

On

Flashes/Off

On

RTD / resistance

INPUT

MODULE

CHANNEL

ST ATUS

0 4

1 5

2 6

3 7

RTD Module

Advertising