Procedure – Rockwell Automation 1746-NR8 SLC 500 RTD/Resistance Input Module User Manual User Manual

Page 75

Advertising
background image

Publication 1746-UM003A-EN-P

Ladder Programming Examples 5-3

This example transfers configuration data and sets the channel enable bits of all
eight channels with a single file copy instruction. The file copy instruction
copies 8 data words from an integer file you create in the SLC’s memory, to the
RTD module’s channel configuration words. This procedure is described
below.

Figure 5.3 Copy File Data Flow

Procedure

1.

1.

1.

1. Using the memory map function to create a data file, create integer file

N10. Integer file N10 should contain eight elements (N10:0 through
N10:7).

2.

2.

2.

2. Using the RSLogix 500 data monitor function, enter the configuration

parameters for all eight RTD channels into a source integer data file N10.
Refer to the Configuration Word Setup illustration for the bit values. See
Appendix B for a channel configuration worksheet.

3.

3.

3.

3. Use the copy file instruction (COP) to copy the contents of integer file

N10 to the eight consecutive output words of the RTD module beginning
with O:3.0. To do this, program a rung as shown below. All elements are
copied from the specified source file to the destination during the first scan
following power up.

Source Data File

Destination Data File

Channel Configuration Word 0

Channel Configuration Word 1

Channel Configuration Word 2

Channel Configuration Word 3

Channel Output Word 0

Channel Output Word 1

Channel Output Word 2

Channel Output Word 3

O:3.0

O:3.1

O:3.2

O:3.3

NI0:0

NI0:1

NI0:2

NI0:3

Address

Address

Channel Configuration Word 4

Channel Configuration Word 5

Channel Configuration Word 6

Channel Configuration Word 7

Channel Output Word 4

Channel Output Word 5

Channel Output Word 6

Channel Output Word 7

NI0:4

NI0:5

NI0:6

NI0:7

O:3.4

O:3.5

O:3.6

O:3.7

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

N10:0

1

0

1

1

1

0

1

1

0

0

1

0

0

0

0

0

N10:1

1

0

1

1

1

0

1

1

0

0

1

0

0

0

0

0

N10:2

1

0

1

1

1

0

1

1

0

0

1

0

0

0

0

0

N10:3

1

0

1

1

1

0

1

1

0

0

1

0

0

0

0

0

N10:4

0

1

0

1

1

1

0

0

0

1

0

1

1

0

0

0

N10:5

0

1

0

1

1

1

0

0

0

1

0

1

1

0

0

0

N10:6

0

1

0

1

1

1

0

0

0

1

0

1

1

0

0

0

N10:7

0

1

0

1

1

1

0

0

0

1

0

1

1

0

0

0

Advertising