Error codes, Error codes -3 – Rockwell Automation 1746-NR8 SLC 500 RTD/Resistance Input Module User Manual User Manual

Page 87

Advertising
background image

Publication 1746-UM003A-EN-P

Module Diagnostics and Troubleshooting 6-3

The following tables explain the function of the channel status LEDs while the
module status LED is turned on.

Table 6.1 Module Status Description

Table 6.2 Channel Status Description

Error Codes

I/O error codes are reported in word S:6 of the SLC processor status file. The
format for the error codes in the status word (S:6) is shown in the illustration
below. The characters denoted as XX in the illustration below represent the slot
number (Hex) for the module. The characters denoted as YY represent the
2-digit hex code for the fault condition.

The error codes applicable to the RTD Module range from 50H to 5AH.
Some of these are non-recoverable errors. For a description of the error codes,
refer to SLC 500 and MicroLogix 1000 Instruction Set Reference Manual,
publication 1747-6.15.

If Module
Status LED is:

Indicated Condition:

Corrective Action:

ON

Proper Operation

No action required.

Off or Flashing

Module Fault

Cycle power. If condition persists,
replace the module or call your
local distributor or Rockwell
Automation for assistance.

LED

Power-up

(1)

(1) Module is disabled during powerup.

Module Operation
(No Error)

(2)

(2) Channel status LED is On if the respective channel is enabled and Off if the channel is disabled.

Module Error

Channel
Error

Ch 0-7 Status

On

On/Off

Off

(3)

(3) Error if channel is enabled.

Flashes

Mod. Status

Off

On

Flashes/Off

On

YY - Error Code (Hex)

X

X

Y

Y

XX - Chassis Slot Number (Hex)