Channel Configuration, Data, and Status 4-21

Table 4.25 Channel 0 through 7 Status Word (I:e.8 through I:e.15) - Bit Definitions

Bit(s)

Define

These bit settings

Indicate this

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0 through 3 Input type

status

0

0

0

0

100

Pt RTD (385)

0

0

0

1

200

Pt RTD (385)

0

0

1

0

500

Pt RTD (385)

0

0

1

1

1000

Pt RTD (385)

0

1

0

0

100

Pt RTD (3916)

0

1

0

1

200

Pt RTD (3916)

0

1

1

0

500

Pt RTD (3916)

0

1

1

1

1000

Pt RTD (3916)

1

0

0

0

10

Cu RTD (426)

(1)

1

0

0

1

120

Ni RTD (618)

(2)

1

0

1

0

120

Ni RTD (672)

1

0

1

1

604

NiFe RTD (518)

1

1

0

0

150

Resistance Input

1

1

0

1

500

Resistance Input

1

1

1

0

1000

Resistance Input

1

1

1

1

3000

Resistance Input

4 through 5 Data format

status

0

0

Engineering units x 1

(3)

0

1

Engineering units x 10

(4)

1

0

Scaled-for-PID

1

1

Proportional Counts

6 through 7 Broken input

status

0

0

Set to Zero

0

1

Set to Upscale

1

0

Set to Downscale

1

1

Not used

8

Temperature
units status

0

Degrees C

(5)

1

Degrees F

(5)

9 through 10 Filter frequency

status

0

0

28 Hz

0

1

50/60 Hz

1

0

800 Hz

1

1

6400 Hz

11

Channel enable
status

0

Channel Disabled

1

Channel Enabled

12

Calibration Error

0

OK

1

Error

13

Broken input

0

OK

1

Error

14

Out-of-range
error status

0

OK

1

Error

15

Configuration
Error

0

OK

1

Error

(1) Actual value at 0°C is 9.042

per SAMA standard RC21-4-1966.

(2) Actual value at 0°C is 100

per DIN standard.

(3) Values are in 0.1 degree /step or 0.1

/step for all resistance input types, except 150

. For the 150

resistance input type, the values are in 0.01

/step.

(4) Values are in 1 degree /step or 1

/step for all resistance input types, except 150

. For the 150

resistance input type, the values are in 0.1

/step.

(5) This bit is cleared (0) when a resistance device, such as a potentiometer, is selected.