Rockwell Automation 1746-NR8 SLC 500 RTD/Resistance Input Module User Manual User Manual

Page 97

Advertising
background image

Publication 1746-UM003A-EN-P

Application Examples 7-5

Configuration setup for bath RTD:

channels 1 and 5

200

Platinum RTD (385)

display temperature to tenths of a degree Celsius or Fahrenheit

zero data word in the event of an open- or short-circuit

28 Hz input filter to provide 60 Hz line noise rejection

use 1.0 mA excitation current for RTD

scaling for 0°C to +60°C

define upper and lower temperature limits

Configuration setup for steam RTD:

channels 2 and 6

1000

Platinum RTD (385)

display temperature to tenths of a degree Celsius or Fahrenheit

zero data word in the event of an open- or short-circuit

50/60 Hz input filter to provide 60 Hz line noise rejection

use 0.25 mA excitation current for RTD

scaling for -20°C to +200°C

Configuration setup for chilled H

2

O RTD:

channels 3 and 7

200

Platinum RTD (385)

display temperature to tenths of a degree Celsius or Fahrenheit

zero data word in the event of an open- or short-circuit

28 Hz input filter to provide 60 Hz line noise rejection

scaling for 0°C to +60°C

define upper and lower temperature limits

Table 7.3 Channel Configuration Worksheet (With Settings Established)

Bit Definitions:
Bits 0 through 3 Input Type Select

0000 = 100

Pt. (385)

0001 = 200

Pt. (385)

0010 = 500

Pt. (385)

0011 = 1000

Pt. (385)

0100 = 100

Pt. (3916)

0101 = 200

Pt. (3916)

0110 = 500

Pt. (3916)

0111 = 1000

Pt. (3916)

1000 = 10

Cu (427)

(1)

1001 = 120

Ni (618)

(2)

1010 = 120

Ni (617)

1011 = 604

Ni-Fe (518)

1100 = 150

Potentiometer

1101= 500

Potentiometer

1110= 1000

Potentiometer

1111= 3000

Potentiometer

Bits 4 and 5

Data Format Select

00 = engineering units, x1

(3)

01 = engineering units, x10

(4)

10 = scaled-for-PID (0 to 16383)
11 = proportional counts (-32768 to +32767)

Bits 6 and 7

Broken Input Select

00 = zero

01 = upscale

10 = downscale

11 = Invalid

Bit 8

Temperature Units
Select

0 = degrees Celsius

1 = degrees Fahrenheit

Bits 9 and 10

Filter Frequency Select 00 = 10 Hz

01 = 50 Hz

10 = 60 Hz

11 = 250 Hz

Bit 11

Channel Enable

0 = channel disabled

1 = channel enabled

Bit 12

Excitation Current
Select

0 = 1.0 mA

1 = 0.25 mA

Bit 13

Calibration Enable

0 = enable

1 = disabled

Bits 14 and 15

Lead Res. Enable

00 = always

01 = periodic

10 = disable

(1) Actual value at 0 °C is 9.042

per SAMA standard RC21-4-1966.

(2) Actual value at 0 °C is 100

per DIN standard.

(3) Values are in 0.1°/step or 0.1

/step for all resistance input types, except 150

. For the 150

resistance input type, the values are in 0.01

/step.

(4) Values are in 1°/step or 1

/step for all resistance input types, except 150

. For the 150

resistance input type, the values are in 0.1

/step.