Publication 1746-UM003A-EN-P

Channel Configuration, Data, and Status 4-13

Table 4.3 Data Formats for RTD Temperature Ranges for 0.25 and 1.0 mA Excitation
Current

Table 4.4 Data Format for 500

Platinum RTD (385)

Table 4.5 Data Format for 1000

Platinum RTD (385)

Table 4.6 Data Format for 500

Platinum RTD (3916)

Table 4.7 Data Format for 1000

Platinum RTD (3916)

Table 4.8 Data Format for 604

Nickel Iron RTD (518)

RTD Input Type

Data Format
Engineering Units x 1

Engineering Units x 10

Scaled-for-PID Proportional Counts

(Default)

0.1°C

0.1°F

1.0°C

1.0°F

100

Platinum (385)

-2000 to +8500

-3280 to +15620

-200 to +850

-328 to +1562

0 to 16383

-32768 to 32767

200

Platinum (385)

-2000 to +6300

-3280 to + 6300

-200 to +630

-328 to +630

0 to 16383

-32768 to 32767

100

Platinum (3916)

-2000 to +6300

-3280 to +6300

-200 to +630

-328 to +630

0 to 16383

-32768 to 32767

200

Platinum (3916)

-2000 to +6300

-3280 to +6300

-200 to +630

-328 to +630

0 to 16383

-32768 to 32767

120

Nickel (672)

-800 to +2600

-3280 to +5000

-80 to +260

-328 to +500

0 to 16383

-32768 to 32767

120

Nickel (618)

(1)

-1000 to +2600

-3280 to +5000

-100 to +260

-328 to +500

0 to 16383

-32768 to 32767

10

Copper (426)

-1000 to +2600

-3280 to +5000

-100 to +260

-328 to +500

0 to 16383

-32768 to 32767

(1) Actual value at 0 °C is 100

per DIN standard.

Excitation Current Data Format

Engineering Units x 1

Engineering Units x 10

Scaled-for-PID Proportional Counts

(Default)

0.1 C

0.1°F

1.0°C

1.0°F

0.25 mA

-2000 to +8500

-3280 to +15620

-200 to +850

-328 to +1562 0 to 16383

-32768 to 32767

1.0 mA

-2000 to +3900

-3280 to +6980

-200 to +390

-328 to +698

0 to 16383

-32768 to 32767

Excitation Current Data Format

Engineering Units x 1

Engineering Units x 10

Scaled-for-PID Proportional Counts

(Default)

0.1 C

0.1°F

1.0°C

1.0°F

0.25 mA

-2000 to +8500

-3280 to +15620

-200 to +850

-328 to +1562 0 to 16383

-32768 to 32767

1.0 mA

-2000 to +500

-3280 to +1220

-200 to +50

-328 to +122

0 to 16383

-32768 to 32767

Excitation Current Data Format

Engineering Units x 1

Engineering Units x 10

Scaled-for-PID Proportional Counts

(Default)

0.1 C

0.1°F

1.0°C

1.0°F

0.25 mA

-2000 to +6300

-3280 to +11660

-200 to +630

-328 to +1166 0 to 16383

-32768 to 32767

1.0 mA

-2000 to +3800

-3280 to +6980

-200 to +380

-328 to +698

0 to 16383

-32768 to 32767

Excitation Current Data Format

Engineering Units x 1

Engineering Units x 10

Scaled-for-PID Proportional Counts

(Default)

0.1 C

0.1°F

1.0°C

1.0°F

0.25 mA

-2000 to +6300

-3280 to +11660

-200 to +630

-328 to +1166 0 to 16383

-32768 to 32767

1.0 mA

-2000 to +500

-3280 to +1220

-200 to +50

-328 to +122

0 to 16383

-32768 to 32767

Excitation Current Data Format

Engineering Units x 1

Engineering Units x 10

Scaled-for-PID Proportional Counts

(Default)

0.1°C

0.1°F

1.0°C

1.0°F

0.25 mA

-2000 to +2000

-3280 to +3920

-200 to +200

-328 to +392

0 to 16383

-32768 to 32767

1.0 mA

-2000 to +1800

-3280 to +3380

-200 to +180

-328 to +338

0 to 16383

-32768 to 32767