Modem Connection

Wire or radio modem communication is possible between the terminal and
controller. Each modem must support full duplex communication. Refer to your
modem user manual for details on settings and configuration.

Figure 11 - Modem Connection

Construct a Null Modem Cable

To construct a null modem cable, refer to this pinout.

Table 45 - Null Modem Pinout

Pin Description

PanelView Plus

Compact 6

9-pin

9-pin

Modem

PanelView Plus

Compact 6

9-pin

25-pin

Modem

Pin Symbol

FG (Frame Ground)

-

-

-

1

FG

TD (Transmit Data)

3

2

3

3

RD

RD (Receive Data)

2

3

2

2

TD

RTS (Request to Send)

7

8

7

5

CTS

CTS (Clear to Send)

8

7

8

4

RTS

SG (Signal Ground)

5

5

5

7

SG

DSR (Data Set Ready)

6

4

6

20

DTR

DTR (Data Terminal Ready)

4

6

4

6

DSR

Terminal

DF1 Port

Modem

Modem

Optical Isolator

Controller