Rockwell Automation 2711PC-xxxx PanelView Plus 6 Compact Terminals User Manual User Manual

Page 47

Advertising
background image

Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014

47

Configuration Mode

Chapter 3

Table 23 - Communication Driver Properties

Field

Description

Valid Values

Serial Properties

Use Auto Config

Automatically or manually configures the baud rate, parity, and error checking
parameters.

Yes (auto configure)
No (manual configure)

Device

The serial device that the terminal is connected to.

PLC-5

®

, SLC

™, MicroLogix™, Logix

Platform

Error Check

Type of error checking used. Error checking is automatically configured if Use Auto Config
is set to Yes.

BCC, CRC

Parity

Type of parity used. Parity is automatically configured if Use Auto Config is set to Yes.

None, Odd, Even

Baud Rate

Data rate at which serial driver communicates. The baud rate is automatically configured
if Use Auto Config is set to Yes.

110, 300, 600, 1200, 4800, 9600,
19200, 38400, 57600, 115200

Stop Bits

Number of stop bits used.

1 or 2

Ack/Poll Timeout

Ack/Poll timeout value in ms.

20…60,000 ms

Max Retries

Number of retries before serial driver fails.

0…10

Station Number

Station number based on a specific device.

0…254

COM Port

Communication port used on the terminal.

1…4

DH-485 Properties

Jumper ID

Identifies the communication card if multiple cards are installed on the terminal.

0…3

Station Number

The unique station number of the terminal on the DH-485 network.

0…31 (decimal)

Baud Rate

The communication rate of the DH-485 network.

9600
19200

MaxStationNumber

The maximum station number on the DH-485 network. The value must be greater than or
equal to the Station Number.

0…31 (decimal)