Check voltages and temperatures, Check the system event log, Start-up messages and codes – Rockwell Automation 2711PC-xxxx PanelView Plus 6 Compact Terminals User Manual User Manual

Page 145: Refer to

Advertising
background image

Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014

145

Troubleshooting

Chapter 8

Check Voltages and Temperatures

Check the battery voltage, processor temperature, and display temperature.

Check the System Event Log

Check the system event log for errors and unexpected behaviors:

From FactoryTalk View ME Station Configuration mode, press Terminal

Settings>System Event Log. Refer to

View and Clear the System Event

Log on page 64

.

From the control panel, open the Hardware Monitor and click the System

Event Log tab. Refer to

System Event Log on page 81

.

Start-up Messages and Codes

The splash screen reports actions and status conditions that occur during startup.
This includes firmware and hardware revision information.

Figure 14 - Start-up Splash Screen

Table 53 - Checking Voltage and Temperature Conditions

Check for These Conditions

Where

What to Do

Battery voltage

< 2.75V DC

From the terminal desktop: Refer

to

Monitors on page 82

From FactoryTalk View ME Station

Configuration mode:
Refer to

View Terminal Information

on page 64

Replace the battery if needed.

Logic board
temperature

>95 °C (203 °F)

From the terminal desktop: Refer

to

Monitors on page 82

Check for obstructed airflow in
the chassis and attempt to
moderate the ambient
temperatures within the
enclosure and surroundings.

Display temperature

>55 °C (131 °F)

From terminal desktop: Refer

to

Temperatures on page 94

:

From FactoryTalk View ME Station

Configuration mode:
Refer to

View the Display

Temperature on page 67

INIT

© 2014 Rockwell Automation, Inc.
All Rights Reserved.

N3

Status or
Error Code

State Message

Logic Module

Hardware Revision

Boot Loader

Firmware Revision

Operating System

Firmware Revision

Progress Bar

RSLinx Enterprise

Firmware Revision

Font Collection

Firmware Revision

Machine Edition

Firmware Revision

FactoryTalk ViewPoint

Firmware Revision

BL

02.12

OS

02

.14

01 OSEX

APP

APPEX

SERV

COMM
FONT

06

.10

01

.03

02

.51

02.10

01.01

05.51

OS Extensions

Firmware Revision

FactoryTalk Services

Firmware Revision

Advertising