Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014

Chapter 2

Install the Terminal

Mounting Clearances

Plan for adequate space around the terminal, inside the enclosure, for ventilation
and cabling. Consider heat produced by other devices in the enclosure. The
ambient temperature around the terminal must be 0…55 °C (32…131 °F).

Panel Guidelines

The terminals are panel-mounted devices intended to mount in the door or wall
of a NEMA rated, UL Type rated, or IP rated enclosure:

Supporting panels must have a mounting thickness of 1.5…4.8 mm

(0.060…0.188 in.).

The material strength and stiffness of the panel must be sufficient to hold

the terminal and maintain an appropriate seal against water and dust.

The panel surface must be flat and free of imperfections to maintain an

adequate seal and NEMA and UL Type ratings.

Panel Cutout Dimensions

Use the full-size template shipped with your product to mark the cutout
dimensions.

Table 12 - Minimum Required Clearances

Product Area

Minimum Clearance

Top

51 mm (2 in.)

Bottom

102 mm (4 in.)

(1)

(1) A clearance of 102 mm (4 in.) is sufficient on the side of the terminal to insert and remove an SD card, and on the bottom of

the terminal for connections.

Side

25 mm (1 in.)

(1)

Back

0 mm (0 in.)

Table 13 - Panel Cutout Dimensions

Terminal Type

Input Type

Height, mm (in.)

Width, mm (in.)

400

Keypad or keypad/touch

123 (4.86)

156 (6.15)

600

Touch

123 (4.86)

156 (6.15)

1000

Touch

224 (8.8)

305 (12.00)