Rockwell Automation 1440-TPR06-00RE XM-360 Process Module User Manual

Page 26

Advertising
background image

Publication GMSI10-UM006C-EN-P - August 2010

18 Installing the XM-360 Process Module

3

Input RTN 1

Current return when channel configured as a loop current
input
Redundant terminal used to jumper terminal to channel Vin (-)
terminal, a requirement for loop current input

4

Input RTN 1

5

Input RTN 2

Current return when channel configured as a loop current
input
Redundant terminal used to jumper terminal to channel Vin (-)
terminal, a requirement for loop current input

6

Input RTN 2

7

Input RTN 3

Current return when channel configured as a loop current
input
Redundant terminal used to jumper terminal to channel Vin (-)
terminal, a requirement for loop current input

8

Input RTN 3

9

Input RTN 4

Current return when channel configured as a loop current
input
Redundant terminal used to jumper terminal to channel Vin (-)
terminal, a requirement for loop current input

10

Input RTN 4

11

Input RTN 5

Current return when channel configured as a loop current
input
Redundant terminal used to jumper terminal to channel Vin (-)
terminal, a requirement for loop current input

12

Input RTN 5

13

Input RTN 6

Current return when channel configured as a loop current
input
Redundant terminal used to jumper terminal to channel Vin (-)
terminal, a requirement for loop current input

14

Input RTN 6

15

Chassis

Connection to DIN rail ground spring or panel mounting hole

16

4-20mA 1 (+)

4-20mA output 1, positive side

17

4-20mA 2 (+)

4-20mA output 2, positive side

18

4-20mA 3 (+)

4-20mA output 3, positive side

19

Vin (+) / Input In 1

Voltage Input 1, positive side when channel configured as a
voltage input
Current Input 1 when channel configured as a current input

20

Vin (-) / Iin Sense 1

Voltage Input 1, negative side when channel configured as a
voltage input
Current sensing 1 terminal when channel configured as a
current input, must be jumpered to channel Input RTN

21

Vin (+) / Input In 2

Voltage Input 2, positive side when channel configured as a
voltage input
Current Input 2 when channel configured as a current input

22

Vin (-) / Iin Sense 2

Voltage Input 2, negative side when channel configured as a
voltage input
Current sensing 2 terminal when channel configured as a
current input, must be jumpered to channel Input RTN

23

Vin (+) / Input In 3

Voltage Input 3, positive side when channel configured as a
voltage input
Current Input 3 when channel configured as a current input

Terminal Block Assignments

No.

Name

Description