50 Configuration Parameters

Name (XM Serial Configuration
Utility only)

A descriptive name to help identify the relay in the
XM Serial Configuration Utility.

Maximum 18 characters

Enable

Enable/disable the selected relay.

Note: The Relay Current Status is set to "Not
Activated" when the relay is disabled. See page 58.

Controls whether the relay must be explicitly reset
after the alarm subsides.

Activation Delay

Enter the length of time for which the Activation
Logic
must be true before the relay is activated. This
reduces nuisance alarms caused by external noise
and/or transient events.

Enter a value from 0 to 25.5 seconds,
adjustable in increments of 0.1
seconds.

Default is 1 second

Sets the relay activation logic.

A or B - Relay is activated when either Alarm A or

Alarm B meets or exceeds the selected Alarm
Status
condition(s).

A and B - Relay is activated when both Alarm A

and Alarm B meet or exceed the selected Alarm
Status
condition(s).

A Only - Relay is activated when Alarm A meets

or exceeds the selected Alarm Status
condition(s).

Options: A only

A or B
A and B

Relay Parameters

Parameter Name

Description

Options/Comments

XM Configuration
Utility

EDS File

Check to Enable

Enabled

Clear to Disable

Disabled

XM Configuration
Utility

EDS File

Latching

Latching
Option

XM Configuration
Utility

EDS File

Check means
latching (relay must
be explicitly reset)

Latching

Clear means
non-latching (relay
is reset once the
alarm condition has
passed)

Nonlatching

XM Configuration
Utility

EDS File

Activation Logic

Logic