Rockwell Automation 1440-TPR06-00RE XM-360 Process Module User Manual

Page 70

Advertising
background image

Publication GMSI10-UM006C-EN-P - August 2010

62 Specifications

Inputs

6 Channels

Isolation

Sensitivity

Input Range

Input Impedance

1 to 6 process DC voltage inputs or loop
current inputs

Up to 250 Volts of isolation for each input

User configurable in software.

User configurable per channel as:

0 to 5 Volts
0 to 10 Volts
4 to 20mA
-5 to 5 Volts
1 to 5 Volts
0 to 20mA

50 ohm Current input / 1 Mohm voltage
input

Outputs

4-20mA Outputs

Accuracy

Isolation

Two isolated banks of three outputs (one
per channel)
600 ohm max load

±1% of full scale max
±0.2% of full scale typical

250 Volts

Indicators

8 LEDs Module Status - red/green

Network Status - red/green
Channel 1 Status - yellow/red
Channel 2 Status - yellow/red
Channel 3 Status - yellow/red
Channel 4 Status - yellow/red
Channel 5 Status - yellow/red
Channel 6 Status - yellow/red

XM-360 Technical Specifications

Product Feature

Specification