Rockwell Automation 1440-TPR06-00RE XM-360 Process Module User Manual

Page 59

Advertising
background image

Publication GMSI10-UM006C-EN-P - August 2010

Configuration Parameters 51

Sets the alarm(s) that the relay will monitor. The
alarm must be from the same device as the relay.
When the Activation Logic is set to "A and B" or "A
or B," you can select an alarm in both Alarm A and
Alarm B. The system monitors both alarms. When
the Activation Logic is set to "A Only," you can
select an alarm only in Alarm A.

Options: Channel 1 value alarm

Channel 2 value alarm
Channel 3 value alarm
Channel 4 value alarm
Channel 5 value alarm
Channel 6 value alarm
Channel 1 rate alarm
Channel 2 rate alarm
Channel 3 rate alarm
Channel 4 rate alarm
Channel 5 rate alarm
Channel 6 rate alarm
Channel 1 difference alarm
(Ch1 minus Ch6)
Channel 2 difference alarm
(Ch2 minus Ch1)
Channel 3 difference alarm
(Ch3 minus 2)
Channel 4 difference alarm
(Ch4 minus 3)
Channel 5 difference alarm
(Ch5 minus 4)
Channel 6 difference alarm
(Ch6 minus Ch5)

Note: You can only select an alarm
that is enabled.

Sets the alarm conditions that will cause the relay to
activate. You can select more than one.

Normal - The current measurement is not within

excess of any alarm thresholds.

Alert - The current measurement is in excess of

the alert level threshold(s) but not in excess of the
danger level threshold(s).

Danger - The current measurement is in excess of

the danger level threshold(s).

Disarm-The alarm is disabled or the device is in

Program mode.

Sensor OOR - The signal from the sensor is

outside the Input Range.

Module Fault - Hardware or firmware failure, or

an error has been detected and is preventing
proper operation of the device.

Options: Normal

Danger
Sensor OOR
Alert
Disarm
Module Fault

Check to enable.
Clear to disable.

Relay Installed

Indicates whether the relay is a physical relay on a
module or a virtual relay. If the relay is a physical
relay, then you can set the Failsafe parameter.

If the relay is a virtual relay, the Failsafe parameter
is not used or it is disabled.

Relay Parameters

Parameter Name

Description

Options/Comments

XM Configuration
Utility

EDS File

Alarm A/B

Alarm
Identifier
A/B

XM Configuration
Utility

EDS File

Alarm Status to
Activate On

Alarm Levels

XM Configuration
Utility

EDS File

Check = Physical
Relay

Installed =
Physical Relay

Clear = Virtual Relay Not Installed =

Virtual Relay