DeviceNet Objects 85

Instance 101 - Measurement Values

This assembly instance can be selected to be sent in response to an I/O Poll
Request from a Master. This instance is the default Poll response selection.

Instance 102 - Measurement Values

This assembly instance can be selected to be sent in response to an I/O Poll
request from a Master.

Table C.11 Instance 101 Data Format (Measurement Values Assembly)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0 - 3

Channel 1 Process (DC) Measurement value

4 - 7

Channel 2 Process (DC) Measurement value

8 - 11

Channel 3 Process (DC) Measurement value

12 - 15

Channel 4 Process (DC) Measurement value

16 - 19

Channel 5 Process (DC) Measurement value

20 - 23

Channel 6 Process (DC) Measurement value

24 - 27

Channel 1 Rate of Change value

28 - 31

Channel 2 Rate of Change value

32 - 35

Channel 3 Rate of Change value

36 - 39

Channel 4 Rate of Change value

40 - 43

Channel 5 Rate of Change value

44 - 47

Channel 6 Rate of Change value

48 - 51

Channel 1 - Channel 6 Difference

52 - 55

Channel 2 - Channel 1 Difference

56 - 59

Channel 3 - Channel 2 Difference

60 - 63

Channel 4 - Channel 3 Difference

64 - 67

Channel 5 - Channel 4 Difference

68 - 71

Channel 6 - Channel 5 Difference

Table C.12 Instance 102 Data Format (Measurement Values Assembly)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0 - 3

Channel 1 Rate of Change value

4 - 7

Channel 2 Rate of Change value

8 - 11

Channel 3 Rate of Change value

12 - 15

Channel 4 Rate of Change value

16 - 19

Channel 5 Rate of Change value

20 - 23

Channel 6 Rate of Change value

24 - 27

Channel 1 Process (DC) Measurement value