Rockwell Automation 1440-TPR06-00RE XM-360 Process Module User Manual

Page 48

Advertising
background image

Publication GMSI10-UM006C-EN-P - August 2010

40 Installing the XM-360 Process Module

Module Status (MS) Indicator

1

Program Mode - Typically this occurs when the module configuration settings are being updated with the XM
Serial Configuration Utility. In Program Mode, the module does not perform its usual functions. The signal
processing/measurement process is stopped, and the status of the alarms is set to the disarm state to prevent
a false alert or danger status.

2

Run Mode - In Run Mode, the module collects measurement data and monitors each measurement device.

Network Status (NS) Indicator

1

Normal condition when the module is not a slave to an XM-440, PLC, or other master device.

Color

State

Description

No color

Off

No power applied to the module.

Green

Flashing Red

Module performing power-up self test.

Flashing

Module operating in Program Mode

1

.

Solid

Module operating in Run Mode

2

.

Red

Flashing

• Application firmware is invalid or not loaded.

Download firmware to the module.

• Firmware download is currently in progress.
• The module power voltage is incorrect.

Solid

An unrecoverable fault has occurred. The module may
need to be repaired or replaced.

Color

State

Description

No color

Off

Module is not online.

• Module is autobauding.
• No power is applied to the module, look at Module

Status LED.

Green

Flashing

Module is online (DeviceNet) but no connections are
currently established.

1

Solid

Module is online with connections currently
established.

Red

Flashing

One or more I/O connections are in the timed-out state.

Solid

Failed communications (duplicate MAC ID or bus-off).