Basic Operations

Powering Up the Module

The XM-360 performs a self-test at power-up. The self-test includes an LED
test and a device test. During the LED test, the indicators will be turned on
independently and in sequence for approximately 0.25 seconds.

The device test occurs after the LED test. The Module Status (MS) indicator is
used to indicate the status of the device self-test.

Refer to Module Indicators on page 39 for more information about the LED
indicators.

Color

State

Description

No Color

Off

• Normal operation within alarm limits on the channel.
• No power applied to the module, look at Module

Status LED.

Yellow

Solid

An alert level alarm condition exists on the channel
(and no sensor-out-of-range or danger level alarm
condition exists).

Red

Solid

A danger level alarm condition exists on the channel
(and no sensor-out-of-range condition exists).

Flashing

A sensor-out-of-range condition exists on the channel.

MS Indicator State

Description

Flashing Red and Green

Device self test is in progress.

Solid Green or Flashing Green

Device self test completed successfully, and the
firmware is valid and running.

Flashing Red

• Device self test completed, the hardware is OK, but

the firmware is invalid.

• Firmware download is in progress.
• Module power voltage is incorrect.

Solid Red

Unrecoverable fault, hardware failure, or Boot Loader
program may be corrupted.