64 Specifications

Relays

Number

Failsafe

Latching

Time Delay

Voting Logic

Reset

Activation On

Up to eight relays when interconnected to
one or two XM-441 Expansion Relay
modules, or
Eight virtual relays whose status can be
used by remote control systems

Normally energized (failsafe), or
Normally de-energized (non-fail-safe)

Latching, or
Non-latching

0 to 25.5 seconds, adjustable in 100msec
increments

Single or paired "And" or "Or" logic applied
to any alarm

Local reset switch on top of module
Digital reset command via serial or
DeviceNet interface

Alarm Status:

Normal
Alert
Danger
Disarm
Sensor-out-of-range
Module fault

Non-Volatile Configuration

A copy of the module configuration is
retained in non-volatile memory from where
it is loaded upon power up*.

*The configuration stored in non-volatile

memory can be deleted only by a module-reset
command sent via the serial interface, using
the Serial Configuration Utility, or via
DeviceNet from any compliant software
application.

Power

Module

Consumption

Heat Production

+21.6 to 26.4V dc

Maximum: 300mA
Typical: 170mA

Maximum: 7.20 Watts (24.6 BTU/hr)
Typical: 4 Watts (14 BTU/hr)

XM-360 Technical Specifications