Connecting the power supply – Rockwell Automation 1440-TPR06-00RE XM-360 Process Module User Manual

Page 28

Advertising
background image

Publication GMSI10-UM006C-EN-P - August 2010

20 Installing the XM-360 Process Module

Connecting the Power Supply

Power supplied to the module must be nominally 24 Vdc (±10%) and must be
a Class 2 rated circuit.

Wire the DC-input power supply to the terminal base unit as shown in Figure
2.8.

Figure 2.8 DC Input Power Supply Connections

47

DNet V (+)

DeviceNet bus power input, positive side (red wire)

48

DNet V (-)

DeviceNet bus power input, negative side (black wire)

49

4-20mA 4 (-)

4-20mA output 4, negative side

50

4-20mA 5 (-)

4-20mA output 5, negative side

51

4-20mA 6 (-)

4-20mA output 6, negative side

Terminal Block Assignments

No.

Name

Description

-

24V dc

Power

Supply

+

-

IMPORTANT

A Class 2 circuit can be provided by use of an NEC Class 2
rated power supply, or by using a SELV or PELV rated
power supply with a 5 Amp current limiting fuse installed
before the XM module(s).

IMPORTANT

24Vdc needs to be wired to terminal 37 (+24 V In) to
provide power to the device and other XM modules linked
to the wired terminal base via the side connector.