Publication GMSI10-UM006C-EN-P - August 2010

Installing the XM-360 Process Module 25

Connecting the Inputs

The XM-360 will accept signals from loop currents or voltage inputs. All six
input channels are electrically isolated from each other and from circuit power
and ground. The isolation provided is up to 250V.

Connecting a Voltage Input

Figures 2.13 to 2.18 show the wiring from a voltage input to the terminal base
unit of the XM-360 module.

Figure 2.13 0-5V Voltage Input to Channel 1 Wiring

IMPORTANT

With all the cable shields connected (six individual input
cables and six output cables), there are not enough chassis
terminals for each shield. Therefore, the cable shields
should be paired as depicted in the following illustrations.
Recommended practice is to use a crimp ferrule.
Alternatively, you can use a separate grounding block
mounted next to the module.

ATTENTION

You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended
practice is to ground the cable shield at the XM-360
terminal base and not at the field device. Any convenient
Chassis terminal may be used (see Terminal Block
Assignments o
n page 17).

TYPICAL WIRING FOR VOLTAGE INPUT

TO XM-360 PROCESS MODULE CHANNEL 1

41

19

20

Process
Output
Voltage

Com

V out

SHIELD

RED

BLK

RED

BLK