Rockwell Automation Liqui-Flo AC Power Modules User Manual

Page 24

Advertising
background image

2-12

LiquiFlo AC Power Modules, Hardware Reference Version 6.4

Step 7. Reapply input power.

Step 8. Verify that parameter P.012 is set correctly for either speed or current.

2.6.2 Wiring the Regulator Board Terminal Strip

The terminal strip on the Regulator board provides terminals for connecting customer
I/O devices. See figures 2.5 and 2.8. The following terminals are provided:

Terminals 1-3: RS-232 connections

Terminals 4-9: encoder connections

Terminals 10-11: analog output connections

Terminals 12-15: analog speed/torque reference connections

Terminals 16-25: 24 VDC digital input connections

Terminal 26: no connection

Terminal 27: 24 VDC common

Terminals 28-31: status relay connections

See chapter 7 for a complete description of, and how to wire, all of the signals
available through the Regulator board terminal strip.

Figure 2.7 – Jumper J17 Settings for Analog Outputs

J17

J17

+10 VDC

Voltage Output Option

Pins 2-3

Current Output Option

Pins 1-2

4-20 mA

(default)