LiquiFlo AC Power Modules, Hardware Reference Version 6.4

Table 9.1 – Resistance Checks

Input

Diode

No.

Meter

Connection

(+) (-)

Component is OK if

resistance (R) is:

Component is defective if:

1

* L1

10 < R < 1 megohm

Continuity (short circuit) or
open when the meter is
connected with reversed
polarity.

2

* L2

3

* L3

4

* L4

5

* L5

6

* L6

7

L1 **

8

L2 **

9

L3 **

10

L4 **

11

L5 **

12

L6 **

* (+) DC Bus Volts power terminal

** (-) DC Bus Volts power terminal

Table 9.1 - Resistance Checks (Continued)