Planning the Installation

3-9

3.2.4 Meeting Encoder Specifications (FVC Regulation Only)

LiquiFlo drives set up for FVC regulation require an encoder for closed-loop operation.
Refer to table A.6 for specifications. Drives set up for V/Hz or SVC regulation do not
require an encoder for feedback because they operate in the open loop mode.

3.2.4.1 Encoder Wiring Guidelines

Encoder connections are considered signal level wiring and, therefore, must be run
separate from control and power wiring. Reliance Electric recommends 18 AWG
unshielded twisted pair wires with 2-3 twists per inch for applications to a maximum
distance of 303 meters (1000 feet). The recommended Reliance Electric part number
is 417900-207CG, 18 AWG, 6 conductor (3 twisted pairs).

3.2.5 Verifying Power Module Output Current Rating Is Greater Than

Motor Full Load Amps

Verify that the LiquiFlo output current rating is equal to or greater than the motor’s full
load current (amps). Table 2.1 lists the output current values.

Table 3.7 – AC Input Line Fuse and Circuit Breaker Selection Values

Model Number

Input Voltage

(+/-10%)

Fuse Rating

Motor Circuit Protector

or Circuit Breaker

41L4060

41LR4060

380-480 VAC

600 A

1

1

Recommended fuse type: UL Class J, 600 V, time-delay, or equivalent.

600 A

50LW4060

50LR4060

380-480 VAC

750 A

2

2

Recommended fuse type: UL Class L, 600 V, time-delay, or equivalent.

800 A

64LW4060

64LR4060

380-480 VAC

1000 A

2

1000 A

120L4060

380-480 VAC

1600 A

2

1500 A