Rockwell Automation Liqui-Flo AC Power Modules User Manual

Page 71

Advertising
background image

Wiring the Regulator Board and RMI Board Terminal Strips

7-15

Table 7.8 - Wiring Signal and Control I/O to the Terminal Strip (Continued)

Terminal

Number

Description

Parameters/Wiring Connections

Wiring a Forward/Reverse Input

19

Digital Input 6

(Default - Forward/Reverse)

Digital input 6 is control function programmable through
parameter P.007. The following parameters must be set:

P.000:Control Source

P.006:Second Menu Password

P.007:Terminal Strip Digital Inputs Configure (Selects and
assigns a control function to digital inputs 6 to 8)

P.008:Terminal Strip Speed Reference Source

(Analog, Motor Operated Potentiometer (MOP), or Preset
Speeds)

P.027Forward/Reverse Configuration

Note that based on the settings of parameters P.000, P.007,
P.008, and r.030 if an RMI board is used, the following
parameters can affect digital input 6:

P.023:MOP Accel/Decel Time

P.024:MOP Reset Configuration

P.031 to P.038: Preset Speeds 1-8

Refer to the LiquiFlo Software Start-Up and Reference
manual for additional information.

Terminal 19 On = Reverse Direction
Diagram shows factory setting. From the encoder end of the
motor, clockwise rotation indicates forward motor movement.

IF P.027 = 1
FORWARD DIRECTION ONLY