Rockwell Automation Liqui-Flo AC Power Modules User Manual

Page 92

Advertising
background image

A-2

LiquiFlo AC Power Modules, Hardware Reference Version 6.4

Table A.2 – Environmental Conditions

Condition

Specification

Operating Temperature (inside an enclosure)

0

°C to 55°C

*

(32°F to 131°F)

*

User-supplied cabinet air cooling system must provide adequate heat dissipation to maintain an internal

temperature not to exceed 55

°C. Refer to table 2.1 for drive air watts loss.

Storage Temperature (Ambient)

-40

°C to 65°C (−40°F to 149°F)

Humidity

5% to 95% (non-condensing)

Table A.3 – Terminal Strip Input Specifications

Signal Type

Terminal(s)

Specification

Speed Reference Input

12-15

10 V (@ 50 K ohm input

impedance or 20 mA)

Digital Inputs (1 - 8)

16

+24 VDC Isolated Supply

17

Remote/Local (Default)

18

Ramp1/Ramp2 (Default)

19

Forward/Reverse
(Default)

20

Function Loss

21

Run/Jog

22

Reset

23

Stop

24

Start

Table A.4 – Terminal Strip Output Specifications

Signal Type

Terminal(s)

Specification

Analog Output

10 -11

scaled signal

0-10 VDC or 4-20 mA

No Connection

26

There is no connection to
terminal 26.

Common

27

+24 VDC common