Rockwell Automation Liqui-Flo AC Power Modules User Manual

Page 72

Advertising
background image

7-16

LiquiFlo AC Power Modules, Hardware Reference Version 6.4

Table 7.8 - Wiring Signal and Control I/O to the Terminal Strip (Continued)

Terminal

Number

Description

Parameters/Wiring Connections

Wiring a Function Loss Input

20

Digital Input 5

(Function Loss)

The following parameters must be set:

P.026:Function Loss Response

A signal must be present at terminal 20 for the drive to be
able to start. See figures 7.1 and 7.2.

The drive is shipped from the factory with a jumper between
terminals 16 and 20 which provides the signal. The function
loss input should be in series with the drive’s external
interlocks. In this case, the jumper must be removed before
the connections are made. See figure 2.6.

Terminal 20 On = No Function Loss

Important: A maintained function loss switch should be

used if P.054 (Level Sense Start Enable) = ON
and P.026 = 1.

Wiring a Run/Jog Input

21

Digital Input 4

(Run/Jog)

The following parameters must be set:

P.000: Control Source

P.020: Jog Speed Reference

P.021: Jog Ramp Accel Time

P.022: Jog Ramp Decel Time

Terminal 21 On = Jog Operation