LiquiFlo AC Power Modules, Hardware Reference Version 6.4

*These are the maximum times from transitioning the input to the drive reacting to the input.

Table A.7 – Input Signal Response Times (Maximum)

Signal Type and Source

Volts/Hertz Regulation*

Vector Regulation*

Keypad START

150 milliseconds

130 milliseconds

Terminal Strip:

START

126 milliseconds

105 milliseconds

STOP, RESET, FL

75 milliseconds

75 milliseconds

Preset Speeds

75 milliseconds

75 milliseconds

Analog Speed/Trim

Reference

16 milliseconds

5 milliseconds

Analog Torque

Reference

N/A

0.5 milliseconds

Network:

START

46 milliseconds +
network transport time

25 milliseconds +
network transport time

STOP, RESET, FL

26 milliseconds +
network transport time

25 milliseconds +
network transport time

Analog Speed/Trim

Reference

5 milliseconds +
network transport time

5 milliseconds +
network transport time

Torque Reference

N/A

0.5 milliseconds +
network transport time

Motor Overload Protection

Electronic Motor
Overload Protection

Provides class 10 motor overload protection according
to NEC article 430. Does not provide speed sensitive
overload protection, thermal memory retention, and
motor over-temperature sensing according to NEC
article 430.126 (A) (2). If such protection is needed in
the end-use product, it must be provided by additional
means.