7-20

LiquiFlo AC Power Modules, Hardware Reference Version 6.4

Table 7.9 – Wiring Signal and Control I/O to the RMI Board Terminal Strip

Terminal

Number

Description

Related Parameters, Specifications, and

Jumpers

Digital Inputs, Control Voltage Output

41
42
43
44

Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4

The four digital inputs are configured using
parameter r.030.

45

+24 VDC Supply, Control Voltage Output

Current-limited and isolated. This supply should
not be used as an external supply for anything
other than the four digital inputs.

46

24 VDC Supply, Control Voltage Input

100 mA per output with an external power supply.
Jumper 24 V EXT

47
48
49
50

Digital Output 1
Digital Output 2
Digital Output 3
Digital Output 4

Configuration: r.031 Timer: r.040
Configuration: r.032 Timer: r.041
Configuration: r.033 Timer: r.042
Configuration: r.034 Timer: r.043
20 mA per output with jumper set to 24 V INT

51

Common

Digital I/O common

Relay Outputs

Relay 1

52
53

Common
Normally Open Contact

Configuration: r.035 Timer: r.044

Relay 2

54
55
56

Normally Closed Contact
Common
Normally Open Contact

Configuration: r.036 Timer: r.045

Relay 3

58
59
60

Normally Closed Contact
Common
Normally Open Contact

Configuration: r.037 Timer: r.046

Analog Inputs, Frequency Input

62

Voltage Signal Input

+10 VDC supply, isolated, stabilized, max.
2.7 mA; jumper setting: V IN (default)

63

Current Signal Input

0 to 20 mA Analog current speed reference
input; jumper setting: C IN

69

Frequency Input

0 to 200 kHz

64

Analog I/O Common

Isolated common for voltage/current or frequency
input.

52

59

60

58

57

56

55

54

53