Rockwell Automation Liqui-Flo AC Power Modules User Manual
Page 58
7-2
LiquiFlo AC Power Modules, Hardware Reference Version 6.4
Table 7.3 – Analog Output Connections (Terminals 10 and 11)
Terminal #
Signal
10
Analog Meter Output
11
Regulator Common
Notes: The output of this terminal is either 0-10 VDC or 4-20 mA as determined by the
setting of jumper J17 on the Regulator board. The analog output must also be
programmed via parameter P.012 for an indication of speed and direction or percent
of torque.
Table 7.4 – Analog Speed/Torque Reference Connections (Terminals 12-15)
Terminal #
Signal
12
Isolated Reference Voltage
13
VDC Speed/Torque Reference
14
mA Speed/Torque Reference
15
Isolated Reference Common
Notes: The analog speed/torque (P.008/U.000) reference is either +/-10 VDC or
+/-20 mA, as determined by the setting of jumper J4 on the Regulator board. The
analog reference can be adjusted using parameters P.009, P.010, and P.011.