LiquiFlo AC Power Modules, Hardware Reference Version 6.4

Table 7.3 – Analog Output Connections (Terminals 10 and 11)

Terminal #

Signal

10

Analog Meter Output

11

Regulator Common

Notes: The output of this terminal is either 0-10 VDC or 4-20 mA as determined by the
setting of jumper J17 on the Regulator board. The analog output must also be
programmed via parameter P.012 for an indication of speed and direction or percent
of torque.

Table 7.4 – Analog Speed/Torque Reference Connections (Terminals 12-15)

Terminal #

Signal

12

Isolated Reference Voltage

13

VDC Speed/Torque Reference

14

mA Speed/Torque Reference

15

Isolated Reference Common

Notes: The analog speed/torque (P.008/U.000) reference is either +/-10 VDC or

+/-20 mA, as determined by the setting of jumper J4 on the Regulator board. The
analog reference can be adjusted using parameters P.009, P.010, and P.011.