Rockwell Automation Liqui-Flo AC Power Modules User Manual

Page 67

Advertising
background image

Wiring the Regulator Board and RMI Board Terminal Strips

7-11

Table 7.8 - Wiring Signal and Control I/O to the Terminal Strip (Continued)

Terminal

Number

Description

Parameters/Wiring Connections

Wiring Analog Outputs

10

11

0-10 VDC or 4-20 mA

Analog Output Reference

Regulator Common

The setting of parameter P.012 selects the terminal strip
analog output source (either speed or torque). Jumper J17
must also be set. See figure 2.5.

The 4-20 mA current selection requires a power supply for
operation. The power can be sourced from the encoder
supply, terminal 4

(15 VDC), or from an external 15V power supply. Note that
the maximum supply current from terminal 4 is 250 mA
(encoder and current source) at 15 V. Terminals 9 and 11 are
internally connected.

Terminal

Strip

+

-

+

-

+

-

Load

(Meter or Analog Input)

Connection to the negative side of the

power supply is only required
when an external 15V power supply is used.