3-2

LiquiFlo AC Power Modules, Hardware Reference Version 6.4

Do not install the drive above 1000 meters (3300 feet) without derating output
power. For every 91.4 meters (300 feet) above 1000 meters (3300 feet), derate the
output current 1%.

Verify that the drive location will meet the environmental conditions specified in table
3.1.

3.1.2 Determining Total Area Required Based on Drive Dimensions

Drive dimensions and weights are listed in table 3.2. Overall drive dimensions are
illustrated in figures 3.1, 3.2, and 3.3 as an aid in calculating the total area required by
the LiquiFlo drives.

Table 3.1 – Environmental Conditions

Condition

Specification

Operating Temperature (inside a NEMA cabinet)

0

°C to +55°C

1

(32° to 131°F)

1

With typical heat rise inside a cabinet, 40

°C ambient outside usually results in 55°C inside.

Storage Temperature (Ambient)

-40

°C to 65°C (−40° to 149°F)

Humidity

5% to 95% (non-condensing)

Table 3.2 – Drive Dimensions and Weights

LiquiFlo

Drive M/N

Frame

Dim. A

Dim. B

Dim. C

Dim. D

Dim. E

Dim. F

Dim. G

Weight

41L4060

41LR4060

B

475 mm

18.69”

800 mm

31.52”

357 mm

14.06”

397 mm

15.63”

711mm

28.00”

39 mm

1.53”

20 mm

0.79”

125 kg

275 lb

50LW4060

50LR4060

C

583 mm

22.96”

971 mm

38.23”

347 mm

13.66”

464 mm

18.25”

787 mm

31.00”

28 mm

1.09”

25 mm

1.00”

168 kg

370 lb

64LW4060

64LR4060

C

583 mm

22.96”

971 mm

38.23”

347 mm

13.66”

464 mm

18.25”

787 mm

31.00”

28 mm

1.09”

25 mm

1.00”

170 kg

375 lb

120L4060

D

1010 mm

39.75”

1245 mm

49.00”

360 mm

14.16”

838 mm

33.00”

1200 mm

47.25”

29 mm

1.12”

25 mm

1.00”

386 kg

850 lb

Advertising