Rockwell Automation Liqui-Flo AC Power Modules User Manual

Page 59

Advertising
background image

Wiring the Regulator Board and RMI Board Terminal Strips

7-3

.

Table 7.5 – Digital Input Connections (Terminals 16-25)

Terminal #

Signal

16

+24 VDC (Current Limited) (For remote control digital inputs only)

17

Digital Input 8 (Remote/Local) - Programmable

18

Digital Input 7 (Ramp1/Ramp2) - Programmable

19

Digital Input 6 (Forward/Reverse) - Programmable

20

Function Loss

21

Run/Jog

22

Reset

23

Stop

24

Start

25

+24 VDC Common

Notes: When a user-installed function loss input, a coast-to-stop pushbutton, or another
external interlock is installed, the factory-installed jumper connecting terminals 16 and
20 must be removed so that a contact, when open, will stop the drive.

Terminals 17, 18, and 19 (remote control inputs 8, 7, and 6) are programmed using
parameters P.007, P.008, and P.031 through P.038. Factory default settings are shown
here in parentheses. Refer to the LiquiFlo Software Start-Up and Reference manual
for more information.

Table 7.6 – Reserved Connections (Terminals 26 and 27)

Teminal #

Signal

26

No Connection

27

+24 VDC Common

Notes: Terminal 26 has no connection and is not used in LiquiFlo applications.
Terminal 27 can be used as a 24 VDC common.