7-18

LiquiFlo AC Power Modules, Hardware Reference Version 6.4

Table 7.8 - Wiring Signal and Control I/O to the Terminal Strip (Continued)

Terminal

Number

Description

Parameters/Wiring Connections

Wiring the Output Status Relays

28

29

30

31

Normally-Closed Contact
(Form B)

Normally-Closed Contact

Common (Form B)

Normally-Open Contact

(Form A)

Normally-Open Contact
Common (Form A)

Both Form A and Form B contacts are rated for 250 VAC/

30 VDC at 5 amps resistive or 2 amps inductive load.

The following parameter must be set:

P.013: Output Relay Configuration

Note that depending on the setting of parameter P.013, the
relay coil will energize (the normally-open contact will close
and the normally-closed contact will open). Refer to the
LiquiFlo Software Start-Up and Reference manual for more
information.