Planning the Installation

3-7

3.2.2.3 Recommended Control and Signal Wire Sizes

The recommended wire sizes to connect I/O signals to the terminal strip on the
Regulator board and RMI board are shown in table 3.6. Recommended terminal
tightening torque is 0.5 Newton-meters (4.5 in-lbs). Operator controls can be up to 303
meters (1000 feet) from the LiquiFlo drive.

Table 3.3 – Recommended Power Wire Sizes for B-Frame Drives

Type of Power Wiring

Drive M/N 41L4060, 41LR4060

with kit M/N 41L4060PM

AC Input Power (R/L1, S/L2, T/L3)

Lug

1

accepts two (2) 300 MCM to 6 AWG

conductors

1

Lugs not provided with standard drive. They are available as part of kit M/N 41L4060PM.

Output Power (U/T1, V/T2, W/T3)

Delta-Wye Transformer (S1 to S6)

Ground (PE)

Table 3.4 – Recommended Power Wire Sizes for C-Frame Drives

Type of Power Wiring

Drive M/N 50LW4060, 50LR4060,

64LW4060, 64LR4060

with kit M/N 64L4060PM

AC Input Power (R/L1, S/L2, T/L3)

Lug

1

accepts two (2) 350 MCM to 4 AWG

conductors

1

Lugs not provided with standard drive. They are available as part of kit M/N 64L4060PM.

Output Power (U/T1, V/T2, W/T3)

Delta-Wye Transformer (S1 to S6)

Ground (PE)

Table 3.5 – Recommended Power Wire Sizes for D-Frame Drives

Type of Power Wiring

Drive M/N 120L4060

with kit M/N 120L4060PM

AC Input Power (R/L1, S/L2, T/L3)

Lug

1

accepts two (2) 800 MCM to

300 MCM conductors

1

Lugs not provided with standard drive. They are available as part of kit M/N 120L4060PM.

Output Power (U/T1, V/T2, W/T3)

Delta-Wye Transformer (S1 to S6)

Ground (PE)