Wiring the Regulator Board and RMI Board Terminal Strips
7-17
Table 7.8 - Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Description
Parameters/Wiring Connections
Wiring the Reset Input
22
Digital Input 3
(Reset)
The following parameter must be set:
•
P.000: Control Source
Terminal 22 On = Reset
Wiring the Stop/Start Inputs
23
24
Digital Input 2
(Stop)
Digital Input 1
(Start)
The following parameter must be set:
•
P.000: Control Source
•
P.025: Stop Type
Terminal 23 Off = Stop
Terminal 24 On Transition = Start
25
24 VDC Isolated Common
Reserved Teminals
26
27
No Connection
+24 VDC Isolated Common
Terminal 26 has no connection and is not used in LiquiFlo
applications. Terminal 27 can be used as a 24V DC common.