Rockwell Automation Liqui-Flo AC Power Modules User Manual

Page 73

Advertising
background image

Wiring the Regulator Board and RMI Board Terminal Strips

7-17

Table 7.8 - Wiring Signal and Control I/O to the Terminal Strip (Continued)

Terminal

Number

Description

Parameters/Wiring Connections

Wiring the Reset Input

22

Digital Input 3

(Reset)

The following parameter must be set:

P.000: Control Source

Terminal 22 On = Reset

Wiring the Stop/Start Inputs

23

24

Digital Input 2

(Stop)

Digital Input 1

(Start)

The following parameter must be set:

P.000: Control Source

P.025: Stop Type

Terminal 23 Off = Stop
Terminal 24 On Transition = Start

25

24 VDC Isolated Common

Reserved Teminals

26

27

No Connection

+24 VDC Isolated Common

Terminal 26 has no connection and is not used in LiquiFlo
applications. Terminal 27 can be used as a 24V DC common.