Rice Lake 820i Programmable Indicator/Controller - Installation Manual User Manual

Page 90

Advertising
background image

Table 9-8. DIG I/O Serial Commands

Command

Description

Values

DON.b#s

Set digital output on (active) at bit b, slot s.

DOFF.b#s

Set digital output off (inactive) at bit b, slot s.

DIO.b#s

Digital input function

OFF, INPUT, OUTPUT, PROGIN, ZERO, NT/GRS,
TARE, UNITS, PRINT, ACCUM, SETPNT,
TIMDATE, ESC, CLEAR, DSPTAR, IDKEY,
KEY0–KEY9, KEYDP, ENTER, NAVUP, NAVDN,
NAVLFT, NAVRGT, KBDLOC, HOLD, BATRUN,
BATSTRT, BATPAUS, BATRESET, BATSTOP,
CLRCN, GROSS, NET, PRIM, SEC, CLRTAR,
CLRACC, TRIGGER

DIO.TRIG_SLOT.b#s

Trigger output slot

NONE, SLOT3

DIO.TRIG_PARAM.b#s

Trigger output parameter

value

Digital inputs and outputs are specified by bit number (b) and slot number (s)

Table 9-9. ALGOUT Serial Commands (Valid Only If Analog Output Card Is Installed)

Command

Description

Values

ALG.ALIAS#s

Analog output alias

name

ALG.SOURCE#s

Analog output source

PROG, SCALEn

ALG.MODE#s

Mode

GROSS, NET

ALG.OFFSET#s

Zero offset

0%, 20%

ALG.ERRACT#s

Error action

FULLSC, HOLD, ZEROSC

ALG.MIN#s

Minimum value tracked

0–9999999

ALG.MAX#s

Maximum value tracked

0–9999999

ALG.ZERO#s

Zero calibration

0–65535

ALG.SPAN#s

Span calibration

0–65535

For commands ending with “#s”, s is the slot number.

Table 9-10. Analog Input Serial Commands (Valid Only If Analog Input Card Is Installed)

Command

Description

Values

XP#s

Extract probe temperature

XPP#s

Extract probe primary temperature

XPS#s

Extract probe secondary temperature

XPT#s

Extract probe tertiary temperature

XI#s

Extract 0–20 mA value

XV#s

Extract 0–10 V value

For commands ending with “#s”, s is the slot number.

86

820i

Installation Manual

Advertising