1l3 cautionary notes on communieatiotis, Current output loiid, Figure 11,3 filter connection example – Toshiba LF494 User Manual

Page 131: Toshiba

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

TOSHIBA

6 F 8 A 0 7 7 4

1L3 Cautionary Notes on Communieatiotis

Observe the following notes and limitations when you use the communications function.

■ Current output loiid

Load resistance:

240 to 1 (including communications line resistance)

Load capacitance:

0

,

22

/ib’ maximum (including commuiiicatiuns line capacitance)

Load inductance: 4mH maximunn (including communiciuions Jiiic inductance)

Cable length; 2 km maximum (approximate value when 1,25 mnr shielded cable

is used nnder standard operating conditions,)

■ Wiring cable

Use a shielded output cable as specified in Table 5.1.

■ Interference on 4-20mA current signal

To communicate with the flowmeter^ a digital signal (amplitude 0,4 to 0,8 V in the case of

500 Q load resistance) with a frequency of 1,2 lo 2,2 kl

i z

is superimposed on the 4-20mA

current signal. If a high^response receiving instrument is connected to the current output line,

the superimposed communications signal may inierfere with the instrument. I’o prevent this

inierrcrencC;, put a low-pass filter wuth a time constant of about

100

ms into the input circuit of

the receiving instrument,

Current output

I

r

—1

4

1

■ ' '1 vvv-------------- ^—1---------

i

^

1

Imd ^^ 1

J

resistance ^ > 1

1

1
1

1
1

]

------------- *—1--------------------- '

1

—[----------'

f

Converter

bllter

Receiving instrument

Figure 11,3 Filter connection example

-

1 3 0

-

Advertising
This manual is related to the following products: