8.2.14 Kate-Of-Change Limit

The ratc-of-changc limit is used lo diminaie high ekclrical noise contained in the process

flow signal.

To check electrical noise, two parameters are defined: rate-of-uhange limit (set in percent

value of the span) and control limit :ime (set in units of seconds). Normally the flowmeter

produces the analog output signal by sampling the How rate signal at 1/24 (or 1/12) of a

second sampling rate, H the sampled value exceeds the set rate-ol-changc limit value based

on the averaged flow rale value up vniil the sampled time, the system will reject that

sampled value and instead the averaged value including the raie-of*change limit value in

place of the rejected sampled value will be output. However, if the limlr-cxceeding sampled

value continues for the same flow direction for more than the preset control limit time, that

diïta will be used as the output signal. The setting ranges for these two parameters are as

follows;

• Rate-of-change limit

0 lo 20 %/sampling rate (in incremenis of 0,5 %)

Where the sampling rate is either ly'24, 1/12 or 1/6 of a second depending on the

excitation frequency as shown below:

Excitât ion freq ucncy

Samplingrate

24

11/.

1/24 sec

12 Hz or

6

Hz

L/12 sec

• Control limit timet 0 to 20 sec {in increments of 1 second)

NOTE

If

“iT

is set in cither of these parameters, the rate-of-changc limit function is disabled.

Proceed as follov-'s to cheek or change the ralc-of-change limit value and the control limit

time.

- 82 -