iNSTaLL THE SENSOrS

System Sensor installation

• Only use the System sensor (CA002500 or equivalent) provided with the unit.

• The sensor wires can be extended up to 500' using a shielded 2-conductor cable

(Belden #8760 or equivalent). Do not ground the shield at the sensor but at the

panel using one of the terminals marked with an “O”.

• Do not run sensor wires in conduit with line voltage wiring.

• Install a 3/8"ID 1/2"NPT immersion well.

• If installing the system sensor on the supply, insert the sensor in a well with heat

paste approximately 5' feet past the boiler loop outlet on the common supply

header but before any major takeoffs. The sensor must be located where it sees

the output of all the boiler stages. If a boiler is piped so that the sensor does not

see its output, the M4-LHS will not sequence the boilers correctly.

• The sensor can also be installed on the return to the boilers after all major returns

and before any boiler. However, when setting the reset ratio and the offset, the

user must consider the temperature drop across the building loop.

Shield

Immersion Well

3/8" ID 1/2" NPT

Immersion Heating System Sensor

Common Supply Pipe

Heating System

Sensor

Sensor Probe

Common Supply Pipe

Strap-On Heating System Sensor

Pipe Insulation

Sensor Probe

Shield

Connect

To control

aLErT

If the HSS can not sense the correct water

temperature, the M4-LHS will not provide

comfortable heat levels.

WarNiNg

Use only the System and Outdoor Air sensors included with the control. Do

not use boiler sensors as it will cause operational problems.

Outdoor Sensor installation

• Only use the Laars Outdoor Air Sensor group included with the unit (CA006500).

• Locate the sensor in the shade on the north side of the building. The sensor

should never be in direct sunlight.

• Be sure the location is away from doors, windows, exhaust fans, vents, or other

possible heat sources.

• The sensor should be mounted approximately 10' feet above ground level.

• Adhere the Outdoor Label provided to the back of the sensor base.

• Use the Enclosure Base bottom knockout for the conduit. Use the locknut to hold

the conduit and enclosure base together. Screw the cover to the base.

• If screws are used to affix the enclosure to the wall, make sure to seal around the

sensor and wall except from the bottom.

• The sensor wires can be extended up to 500' using shielded 2-conductor cable

(#18/2). Do not ground the shield at the sensor but at the control using the

terminal marked with an “O”.

• Do not run sensor wires in conduit with line voltage wiring.

aLErT

Determining the proper location of the Outdoor Sensor is very important. The M4-LHS will base

the heat on the outdoor temperature information it receives from this location. If the sensor is in the

sun, or covered with ice, its reading will be different from the actual Outdoor Temperature (OD).

System Sensor

In Well

Shield

Not connected

Well Locknut

Sensor in Well

Well

Sensor 2-Conductor

Shielded Cable

System

Strap-On

Sensor

Shield

Not connected

Plastic

Tie-Wraps

Around Pipe

Strap-On Sensor

Immersion Sensor

Outdoor Sensor

snap-in location

Shield

not connected

Conduit

Outdoor Label

on back of Sensor

Outdoor Sensor

Mounting

screws

location

Seal around

sensor and wall

Outdoor

drip-hole

Conduit

Well

Sensor

in well