M4-LHS Installation and Operation Manual

3

HYBRID LOGIC OVERVIEW

In response to new advancement in condensing boiler design and size, many applications utilize multiple condensing boilers in

addition to the non-condensing boilers. That triggered Laars's design of the M4-LHS. It is intended to manage the two groups of

When Hybrid is selected

as the Boiler Type, the M4-LHS will select the lead group based on the Target temperature switching set point. See "Switch Set

Point" on page 20. The Condensing group of boilers will be the Lead group when the System Temperature is below the System Target

Switching Set Point. However, when the System Temperature rises above the Switching Set Point, the Non-Condensing boiler group

will be the lead group and the Condensing Group will be the lag group.

Basically, the M4-LHS will allow the condensing group of boilers to operate as along as the System sensor is below the Switching Set

Point. See"Switch Set Point" on page 20. During that period, if additional output boilers are needed, the M4-LHS may energize the

Non-Condensing boilers to meet the load depending on the Heavy Load Sequence 2nd Group setting. See"Heavy Load Sequence 2nd

Group" on page 21. When less output is required the M4-LHS will de-energize the lag group of boilers prior to de-energizing the lead

group of boilers.

To eliminate any short-cycling due to rapid changes in the Target Temperature used in the switching, an adjustable Switching Delay

has been incorporated. See"Switch Delay" on page 21.

Each of the condensing and non-condensing groups of boilers can be either modulating or staging. Modulating boilers can be of

4-20mA modulating signal or 0-10V modulating signal. See "Modulating Output Type" on page 23. Staging boilers can be On/Off,

2-Staeg, 3-Stage, or 4-Stage. See "Staging Output Type" on page 22.

For Hybrid settings, See "Boiler Type" on page 19.

To set the Condensing and Non-Condensing boiler types See "HYBRID Modulating Boiler Settings" on page 22.

Above the Switch Set Point

Non-Condensing are the Lead Group

Condensing are the Lag Group

Target Switch

Set Point

= 120°F

Below the Switch Set Point

Condensing are the Lead Group

Non-Condensing are the Lag Group

120°F

140°F

100°F

SWITCH MODE = Target Temperature

SYSTEM
A
B
C
D

1 2

RUN

PROGRAM

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

22

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

PROVE

/DHW

SHUTDOWN

/TSTAT

/SETBACK

OD=

25 oF

SYS=

145 oF

<<A>>

B

100%

52%

System

Temp

SYSTEM
A
B
C
D

1 2

RUN

PROGRAM

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

22

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

PROVE

/DHW

SHUTDOWN

/TSTAT

/SETBACK

OD=

25 oF

SYS=

145 oF

<<A>>

B

100%

52%

Above the Switch Set Point

Condensing are the Lead Group

Non-Condensing are the Lag Group

Outdoor Switch

Set Point

= 30°F

Below the Switch Set Point

Non-Condensing are the Lead Group

Condensing are the Lag Group

30°F

50°F

10°F

SWITCH MODE = Outdoor Temperature

COND

COND

NON-

COND

NON-

COND

NON-

COND

NON-

COND

COND

COND

Outdoor

Temp

SYSTEM
A
B
C
D

1 2

RUN

PROGRAM

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

22

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

PROVE

/DHW

SHUTDOWN

/TSTAT

/SETBACK

OD=

25 oF

SYS=

145 oF

<<A>>

B

100%

52%

SYSTEM
A
B
C
D

1 2

RUN

PROGRAM

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

22

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

PROVE

/DHW

SHUTDOWN

/TSTAT

/SETBACK

OD=

25 oF

SYS=

145 oF

<<A>>

B

100%

52%

NON-

COND

NON-

COND

COND

COND

COND

COND

NON-

COND

NON-

COND