Bacnet pics statement – LAARS M4-LHS - Installation Manual User Manual

Page 47

Advertising
background image

HT# 059295-00

A

M4-LHS installation and Operation Manual

47

BaCNET PiCS STaTEMENT

Product

Model Number Protocol revision Software Version Firmware Version

M4-LHS BACnet Control

Varies

1.5

2.0

2.0

Vendor

Vendor iD

address and Phone

Laars

Product Description

M4-LHS control for hot water heating applications. (see http://www.Laars.com for more information)

BACnet Standardized Device Profile (Annex L)

Product

Device Profile

M4-LHS BACnet Control

BACnet Application Specific Controller (B-ASC)

Supported BiBBs (annex k)

Supported BiBBs BiBB Name

DS-RP-B

Data Sharing-ReadProperty-B

DS-WP-B

Data Sharing-WriteProperty-B

DM-DDB-B

Device Management-Dynamic Device Binding-B

DM-DOB-B

Device Management-Dynamic Object Binding-B

DM-DCC-B

Device Management-DeviceCommunicationControl-B

Standard Object Types Supported

Object Type

Creatable Deletable

Analog Value

No

No

Binary Value

No

No

Multi-State Value

No

No

Device

No

No

Data Link Layer Options (annex J)

Product

Data Link

Options

M4-LHS BACnet Control

BACnet MS/TP

Baud Rates: 9600, 19200, 38400

Segmentation Capability

Segmentation Type

Supported

Window Size (MS/TP product limited to 1)

Able to transmit segmented messages

No

Able to receive segmented messages

No

Device address Binding

Product

Static Binding Supported

M4-LHS BACnet Control

No

Character Sets

Product

Character Sets supported

M4-LHS BACnet Control

ANSI X3.4

Advertising