Control layout, M4-lhs, A b c d – LAARS M4-LHS - Installation Manual User Manual

Page 6: System, Hybrid control

Advertising
background image

HT# 059295-00

A

6

M4-LHS installation and Operation Manual

ParT NuMBEr # Ca009200

1 2

RUN

PROGRAM

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

20

19

21

24

23

29

25

27

26

28

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

+

mA

22

-

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

PROVE

/DHW

SHUTDOWN

/SETBACK

CAUTION: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required

to de-energize the equipment before servicing.

/TSTAT

A
B
C
D

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 30VA MAX

INPUT RATINGS:

USE COPPER WIRE,

CLASS 1 WIRE ONLY.

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

99RA

SYSTEM

M4-LHS

HYBRID CONTROL

STAGE

MENU

OD=35

o

F

SYS=145

o

F

<<A>>

B

100%

50%

The digital display shows the system status, set point,

lead stage <in brackets>, and status of each stage.

To view and adjust settings, press the appropriate buttons.

LED indicates the

associated relay status.

Buttons function is presented on

Bottom Row of display.

Program Switch to restrict access to

function changes. This switch is

covered with Wiring Enclosure.

120VAC Power

Four N.O. Boiler startup relay

outputs. Each is wired in series

with each boiler's limit circuit.

System Output controls

pumps, valves, or other

system components.

Four modulation/staging outputs can be

4-20mA or Voltage. Go to Startup Menu

to determine the type of output for each stage.

When connecting the control Outdoor Air

Sensor and System Sensor, no polarity is

observed. Prove terminals must be connected

for control to operate boilers.

Connect Extension panels to add

additional stages using a RJ11 cable(cable

provided with Extension) and RJ45-RJ11

Adaptor (Supplied with control) only or add

X-BAC BACnet Interface Module using RJ45

(cable provided with X-BAC Module)

CONTrOL LaYOuT

Advertising