Outdoor reset concept, Reset ratio curves, Reset ratio/outdoor reset – LAARS M4-LHS - Installation Manual User Manual

Page 5

Advertising
background image

HT# 059295-00

A

M4-LHS installation and Operation Manual

5

OuTDOOr rESET CONCEPT

The M4-LHS has multiple operating modes that satisfy most hydronic systems. It

changes the System Set Point based on outdoor temperature (Outdoor Reset). The

M4-LHS varies the temperature of the circulating heating water in response to

changes in the outdoor temperature. The heating water temperature is controlled

through the modulation or sequencing of the stages.

The M4-LHS also controls the system circulating pump with an adjustable Outdoor

Cutoff. When the outdoor temperature is above the Outdoor Cutoff, the pump

is off and no heating water is circulated through the system. When the outdoor

temperature drops below the Outdoor Cutoff, the system pump relay is activated

and the heating water circulates through the system. The temperature of the heating

water is controlled by the Reset Ratio, Water Offset, and changes with Outdoor

Temperature.

reset ratio/Outdoor reset

When a building is being heated, heat escapes through the walls, doors, and windows

to the colder outside air. The colder the outside temperature, the more heat escapes.

If you can input heat into the building at the same rate that it is lost out of the

building, then the building temperatures will remain constant. The Reset Ratio is an

adjustment that lets you achieve this equilibrium between heat input and heat loss.

The starting point for most systems is the 1.00 (OD):1.00 (SYS) (Outdoor

Temperature : Heating Water Temperature) ratio. This means that for every degree

the outdoor temperature drops, the temperature of the heating water increases by one

degree. The starting point of the curves is adjustable, but comes factory selected

at 70

°

F Outdoor Temperature and 100

°

F Water Temperature. For example with

a 1.00 (OD):1.00 (SYS) ratio, if the outdoor temperature is 50

°

F, this means the

temperature has fallen 20

°

from the starting point of 70

°

F. Therefore, the heating

water temperature shall increase 20

°

to 120

°

F.

Each building has different heat loss characteristics. A very well insulated building

will not lose much heat to the outside air, and may need a Reset Ratio of 2.00

(OD):1.00 (SYS) (Outdoor:Water). This means the outdoor temperature would

have to drop 2° to increase the water temperature 1 degree. On the other hand, a

poorly insulated building with insufficient radiation may need a Reset Ratio of 1.00

(OD):2.00 (SYS). This means that for each degree the outdoor temperature dropped

the water temperature increases by 2°. The M4-LHS has a full range of Reset Ratios

to match any buildings heat loss characteristics.

A heating curve that relies not only on Outdoor Temperature but also on the type

of radiation improves heat comfort. The following are suggested initial settings for

different types of radiation based on average building insulation and heat loss. The

contractor can fine tune these adjustments based on the specific building need.

Type of radiation in Building

reset ratio

Offset

Radiators (Steel & Cast Iron)

1.00 (OD) : 1.00 (SYS)

0˚F

Baseboard (Finned copper tube& Cast Iron)

1.00 (OD) : 1.00 (SYS)

0˚F

Radiant (High Mass/Concrete)

4.00 (OD) : 1.00 (SYS)

-10˚F

Radiant (Low Mass/Joists)

2.00 (OD) : 1.00 (SYS)

-10˚F

Fan Coils & Air Handlers

1.00 (OD) : 1.00 (SYS)

20˚F

Outdoor Temperature

W

at

er

T

em

pe

ra

tu

re

70

40

50

60

130

120

110

100

Outdoor Temperature

W

at

er

T

em

pe

ra

tu

re

70

40

50

60

110

100

90

80

Outdoor Temperature

W

at

er

Te

m

pe

ra

tu

re

70

40

50

60

150

140

130

120

1:4

With a 0° Offset, the
Reset curves begin at
100° Water Temperature.

With a -20° Offset, the
Reset curves begin at
80° Water Temperature.

With a +20° Offset, the
Reset curves begin at
120° Water Temperature.

1:4

1:4

1:1

1:1

1:1

4:1

4:1

4:1

90

100

+20 Offset

-20 Offset

Outdoor Temperature

W

at

er

T

em

pe

ra

tu

re

70

40

50

60

130

120

110

100

1:4

1:1

4:1

Colder

Warmer

Outdoor Temperature (in °F)

70

60

50

40

20

30

0

-10

10

-20

100

120

110

130

140

150

160

180

170

190

200

210

220

1:3

1:2

1:1.5

1:1.25

1:1

1.25:1

1.5:1

2:1

3:1

4:1

W

ater

Temperature (in °F)

Reset Ratio Curves

Reset Ratio is Presented as

Outdoor Temp. : Water Temp. Ratio

1:4

Advertising