Hybrid operating menu, Alert, 0 min – LAARS M4-LHS - Installation Manual User Manual

Page 28: 10 min

Advertising
background image

HT# 059295-00

A

28

M4-LHS installation and Operation Manual

aLErT

To be able to change the M4-LHS

settings the Program/Run Switch must

be set to Program. The switch is located

under the Enclosure Wiring Cover for

security. The Enclosure Wiring Cover

can be secured using a lock.

-------- SETTINGS ----

Season

Winter

System Target 140

o

F

<System Settings>

<Maintenance>

<System Startup>

BACK ▲ ▼ SELECT

OD=

55

o

F SYS=

143

o

F

<<A>>

B

67%

22%

STAGE ◄ ► MENU

----- SEASON -----

Winter

Summer

BACK ▲ ▼ SAVE

-- SYSTEM TARGET --

1.00

o

OD = 4.00

o

Sys

1.00

o

OD = 3.00

o

Sys

1.00

o

OD = 2.00

o

Sys

1.00

o

OD = 1.50

o

Sys

1.00

o

OD = 1.25

o

Sys

1.00

o

OD = 1.00

o

Sys

1.25

o

OD = 1.00

o

Sys

1.50

o

OD = 1.00

o

Sys

2.00

o

OD = 1.00

o

Sys

3.00

o

OD = 1.00

o

Sys

4.00

o

OD = 1.00

o

Sys

BACK ▲ ▼ SAVE

----- SETTINGS 1 ----

Setback

10

o

F

Purge Delay 1.0min

System Run-On 10min

Lead Rotation Time

<More Settings>

BACK ▲ ▼ SELECT

------- SETBACK -------

10

o

F

[

]

BACK ▲ ▼ SAVE

--- PURGE DELAY ---

1.0 min

[

]

BACK ▲ ▼ SAVE

-- SYSTEM RUN-ON --

10 min

[

]

BACK ▲ ▼ SAVE

-- LEAD ROTATION --

Manual

Time

Last-On

BACK ▲ ▼ SAVE

----- SETTINGS 2 ----

Standby Time 10min

Last Stg Hold 5

o

F

<Lead Stages>

<Staging Settings>

<Mdlating Settings>

<Day/Night Schdule>

BACK ▲ ▼ SELECT

-- STANDBY TIME --

10 min

[

]

BACK ▲ ▼ SAVE

LAST STAGE HOLD

5

o

F

[ ]

BACK ▲ ▼ SAVE

--- LEAD STAGES ---

Cond Lead

A

Non-Cond Lead

C

BACK ▲ ▼ SAVE

- STAGE SETTINGS -

Reaction Time 2min

Minimum Runtime

2min

BACK ▲ ▼ SAVE

MODULATION SETTINGS

Gain

+0

Lag Delay

0min

Soft-Off Delay 45sec

BACK ▲ ▼ SAVE

DAY/NIGHT SCHEDULE

Set Time

**:**

Day Schedule 6:00a

Night Schedule

8:00p

BACK ▲ ▼ SAVE

------- OFFSET ------

+0

o

F

[ ]

BACK ▲ ▼ SAVE

- OUTDOOR CUTOFF -

65

o

F

[

]

BACK ▲ ▼ SAVE

MINIMUM WATER TEMP

70

o

F

[ ]

BACK ▲ ▼ SAVE

MAXIMUM WATER TEMP

200

o

F

[

]

BACK ▲ ▼ SAVE

HYBriD OPEraTiNg MENu