Modulating boiler settings, Boiler number, Modulating output type – LAARS M4-LHS - Installation Manual User Manual

Page 23: Modulating mode, Warning

Advertising
background image

HT# 059295-00

A

M4-LHS installation and Operation Manual

23

MODuLaTiNg BOiLEr SETTiNgS

Boiler Number

Adjustable from 1 to 15

Default: 1

Button: MENU/<System Startup>/Boiler Type/.../Boiler Number

• Select the number of modulating boilers.

Modulating Output Type

4-20mA, 0-10V, 1-10V (Custom) Outputs

Default: 1-10v Custom

Button: MENU/<System Startup>/..../Boiler Number/Output A Type

• The M4-LHS will offer the capability of controlling a variety of modulating signals.

Each boiler can be configured to have a different modulating signal. Check the boiler to

determine its signal requirements.

• When using the Extension, connect it to the M4-LHS prior to configuring the Output Type.

Otherwise, the M4-LHS might not recognize the Extension stages.

Modulating Mode

Normal, Parallel

Default: Normal

Button: MENU/<System Startup>/..../Output A Type/Modulating Mode

• Some modulating boilers perform better at higher modulation. For these units, it is

advantageous to run one unit at high modulation than several units at lower modulation. If

the units used are of this type, select Normal. This is the recommended setting for typical

steel and cast iron boilers or boilers with low turndown ratios.

• There are many condensing boilers that run more efficiently at lower modulation. If it

is more energy efficient to run several units at lower modulation than one at high, select

Parallel. This is typically used on condensing boilers or boilers with high turndown ratios.

• For best Parallel performance, set the Modulation Start % to be equivalent to the lowest

firing rate of the boiler multiplied by 2. That is, if the lowest firing of the boiler was 20%,

set your Modulation Start% to 40%. See "Modulation Start %" on page 40.

Set the Lag Delay to 0 for better parallel performance. See "Lag Delay" on page 33.

WarNiNg

Make sure that boiler modulation

wiring matches the signal selected.

Warranty will not cover failed

components caused by improper

wiring. See "Wiring the Boilers" on

page 14.

-- BOILER NUMBER --

2

[ ]

BACK ▲ ▼ SAVE

- MODULATING MODE -

Normal

Parallel

BACK ▲ ▼ SAVE

OUTPUT A TYPE --

4-20mA

0-10volt

0-5volt

2-10volt

1-5volt

BACK ▲ ▼ SAVE